G4500
Portable Power Quality Analyzer
The BlackBox G4500 portable takes power quality analyzers & power monitoring to a whole new level by using the revolutionary PQZIP patent algorithm. The unique algorithm Enables you to measure, store & analyze (continuously) waveform signals regardless their size
Features
PQZIP inside
Continuous waveform recording
Trigger free setup
5,000 power parameters @ 1/2
Cycle resolution
Easy deployment
Class A
Far surpassing the highest standards set by the industry, the BLACKBOX device series complies with standards for: aggregations, time clock uncertainty, flagging, and transient influence quantities.
Superior Accuracy
Elspec’s pioneering measurement method utilizes a dual-range gain of 2 x 16 Bit to yield, a superior accuracy far surpassing IEC 61000-4-30 Class A requirements, thereby capturing the finest details & deviations in Power Quality parameters.
Synchronized Monitoring
A unique time synchronization algorithm assures that logged data from multiple units is synchronized & isplayed on the same time scale with typical 0.1 ms resolution. Every event on a grid is accurately analyzed for precise root cause analysis, behavior propagation, and traced to its source.
Applications
UTILITIES (TRANSMISSION, DISTRIBUTION, GENERATION)
Optimizes protective equipment configuration and substation automation solutions
Ensures a reliable and consistent supply of energy
Evaluates the performance of breakers and relays
Identifies and manage peak demand
Real time power quality monitoring to meet any international standard
Produces detailed & comprehensive statistical records
ENERGY CONSUMER (CRITICAL POWER, INDUSTRIAL, COMMERCIAL, ETC.)
Measures and analyzes system efficiency, provides solutions and increases profits
Negotiates capabilities with power providers
Detects electric bill inconsistencies
Avoids power quality compliance issues
Monitors and analyses power quality in real time
Continuous Waveform Recordings
The G4500 portable power quality analyzer is able to record and store all electrical waveform continuously for more than a year, with no gaps in the data. The G4500 portable power quality analyzer offers a clear and comprehensive picture of the conditions before, during, and after an event.
Supreme Trends Resolution
The G4500 portable power quality meter measures and records 5,000 power parameters continuously at a resolution of ½ cycles, 10/12 cycles, 150/180 cycles, 10 min and 2 hours of which, any given resolution is calculated for display and reporting purposes. Hence, there is no need to select which parameters to log, and more importantly, which parameters to ignore.
Harmonics & Inter-Harmonics Analysis
The G4500 portable power quality analyzer has two FFT engines for harmonics analysis: Cycle by Cycle: performs FFT at 1 cycle resolution for extended bandwidth. This engine provides 512 harmonics order at 50Hz resolution. 10/12 Cycles: performs FFT 10/12 cycles resolution for extended resolution and sub-grouping calculation. This engine provides the magnitude and angle of 512 spectrum components at 5Hz resolution.
Comprehensive Event Mechanism
The G4500 portable power quality meter is designed to detect any event occurring on your system. The mechanism allows you to configure events on any measured parameter (more than 1,000) and/or I/O ports. The event mechanism supports out-of-limit events as well as rate of changed limits. The G4500 analyzer is capable of recording waveform signals continuously. The event configuration doesn’t trigger the recording but rather stores summary logs including start and end time, duration, severity and magnitude of the event. All events can be displayed in a tabular or scatter charts as CBEME/ITIC.
Specifications
Waveform Sampling |
|
| Voltage Sampling Rate | 1024 Samples/Cycle |
| Current Sampling Rate | 256 Samples/Cycle |
| Voltage Harmonics (Individual, Even, Odd, Total) Up to – | 511Th |
| Current Harmonics (Individual, Even, Odd, Total) Up to – | 127Th |
| Type of Analog to Digital Converter | 16/201 bit |
Storage Capacity |
|
| Internal Memory | 32 GB / 32TB2 |
Power Quality Analysis |
|
| Transient Detection, Microseconds (50Hz/60Hz) | 19.5 / 16.3 μs |
Communication Ports |
|
| Ethernet Ports | 3 |
| Wi-Fi Communications (802.11g) | 1 |
| Power Over Ethernet (PoE-Out) | 1 |
| Digital Input | 4 |
| RS-232 | 1 |
| RS-485 | 1 |
Physical |
|
| Dimensions | 314 × 84 × 271 mm |
| Weight | 3.7 kg |
Control |
|
Applicable Standards |
|
| Measurement Standards | EN50160, IEEE1159, IEEE519, IEC61000-4-15, IEC61000-4-7, IEC61000-4-30 Class A EMC Standards EN61326, CFR47FCC, CISPR11 Group 1, FCC PART 15 Subpart B, EN61010-2, IEC61000-3-3, IEC61000-4-2, IEC61000-4- 3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-11 |
| Environmental Standards | IEC60068-2-1, 2, 6, 27, 30, 75 |
| Safety Standards | EN61010-1:2001 2nd Edition |
Power Supply |
|
| Operating Range | 100-260 VAC 50/60 Hz, 100-300 VDC |
| Auxiliary DC Supply | 48 VDC |
| Auxiliary Supply | PoE In According to 802.3af |
| Battery Backup | 2 Hours |
Environmental Conditions |
|
| Operation Temperature | 0°C – 50°C (32°F – 122°F) |
| Storage Temperature | -20°C – 60°C (-4°F – 140°F) |
Time Synchronization |
|
| Real Time Clock | ±1 Second per 24 Hours |
| GPS | 100-200 μs |
| IRIG B | 100-200 μs |
| SNTP Server | 50-100 μs |
| DCF-77 | ±15 ms |
Voltage Channels |
|
| Voltage Channels | 4 (3 Phases + Neutral) + 1 DC |
| Nominal Full Scale | 1000V |
| Maximum Peak Measurement | 8000V |
| Input Impedance | 3MΩ |
| Uncertainty | 0.1% of Nominal |
Current Channels |
|
| Current Channels | 4 (3 Phases + Neutral) + 1 Ground/DC |
| Current Channels Receive From Clamp | I1-I4: 0-10 Vpk, I5: 0-3 Vpk |
| Uncertainty | 0.1% ±0.1 mV |
Frequency Measurement |
|
| Fundamental Frequency | 42.5 Hz to 69 Hz |
| Frequency Resolution | 10 mHz |
| Frequency Accuracy | ±10 mHz |
Optional Accessories
1 – 6A Mini Clamp
Ordering Information SOA-0010-0500
Measurement Range 6/60AAC
Output Signal 100m V/A
Operating Temperature – 20°C to + 60°C
Cable Length 1.2m
DC Current Clamp
Ordering Information SOA-0270-14001
Measurement Range 1,500A DC / 1,000A AC
Output Signal 1m V/A, 10m V/A
Operating Temperature – 10°C to + 55°C
Cable Length 1.4m
100A Mini Clamp
Ordering Information SOA-0180-5000
“Hole” Dimensions 10mm Max
Measurement Range Up to 100APK AC
Output Signal 100m V/A
Operating Temperature – 20°C to + 60°C
Cable Length 1.2m
Custom Clamp 3-Flexible Current Probes
Ordering Information SOA-3003-0270
Measurement Range 30A/300A/3000A AC RMS
Operating Temperature – 20°C to + 65°C
Probe Cable Length 610mm (24”)
Probe Cable Diameter 194mm (7.5”)
3000a Flexible Current Clamps
Ordering Information SOA-9045-3001
Measurement Range 90A – 4,200A
Operating Temperature – 20°C to + 60°C
Cable Length 2m
Probe Length 80cm
300A Flexible Current Clamps
Ordering Information SOA-9091-3000
Measurement Range 9A – 1,050A
Operating Temperature – 20°C to + 60°C
Cable Length 2m
Probe Length 45cm
GPS